Type-T T/C

The copper positive leg and constantan negative leg produce a thermoelectric voltage related to the temperature difference between the sensing junction and reference connections. Type T has its own nonlinear reference curve. A single microvolts-per-degree figure is only a local sensitivity, not a conversion constant for the whole range.

The copper and constantan leads join at the sensing point. A temperature difference between that point and the reference connections produces a small voltage. Measure the reference temperature, convert it to the equivalent thermocouple voltage, add the measured voltage, then use the correct type's conversion curve. Do not simply add temperatures as if the response were perfectly linear.

In plain terms

Think of it as a thermometer that compares two places. To find the sensing-point temperature, it also needs to know the temperature where its wires meet the measuring instrument.

Why designers use it

Best for

Key specifications

When not to use it

Common mistakes

Where you will find it

A short history

This standard thermocouple type uses copper for the positive leg and constantan for the negative leg. Standard reference curves relate its voltage to temperature, but the sensor measures a temperature difference: cold-junction compensation is still needed. Probe construction, atmosphere and wire size determine the usable range of a real assembly.